Session Dates
24 Aug 2012 - 25 Aug 2012
Keywords and Phrases
cold formed steel; shear connector; ductility; strength resistance; composite beam; push test
Abstract
In this study, experimental tests were conducted to investigate the ductility and strength capacity of new shear connector. Push test specimens were prepared and tested according to EN1994-1-1 standard. The push test specimen consists of two cold-formed steel lipped channel sections oriented back-to-back to form an I-section beam, transverse metal deck and normal concrete slabs grade C25/30. Angle brackets were obtained from the same section of the beam and fastened to the web of steel beam to provide the shear connection. Two shear connectors were tested namely; “SC1” and “SC2” shear connectors. Both shear connectors showed a ductile behavior and had satisfied the ductility requirements of EN1994-1-1 standard. It was concluded that the ductile behavior of shear connectors could enhance the design of composite beam.
Department(s)
Civil, Architectural and Environmental Engineering
Research Center/Lab(s)
Wei-Wen Yu Center for Cold-Formed Steel Structures
Meeting Name
21st International Specialty Conference on Cold-Formed Steel Structures
Publisher
Missouri University of Science and Technology
Document Version
Final Version
Rights
© 2012 Missouri University of Science and Technology, All rights reserved.
Document Type
Article - Conference proceedings
File Type
text
Language
English
Recommended Citation
Bamaga, S. O.; Tahir, M. M.; and Tan, C. S., "Push Tests on Innovative Shear Connector for Composite Beam with Cold-formed Steel Section" (2012). CCFSS Proceedings of International Specialty Conference on Cold-Formed Steel Structures (1971 - 2018). 1.
https://scholarsmine.mst.edu/isccss/21iccfss/21iccfss-session5/1
Push Tests on Innovative Shear Connector for Composite Beam with Cold-formed Steel Section
In this study, experimental tests were conducted to investigate the ductility and strength capacity of new shear connector. Push test specimens were prepared and tested according to EN1994-1-1 standard. The push test specimen consists of two cold-formed steel lipped channel sections oriented back-to-back to form an I-section beam, transverse metal deck and normal concrete slabs grade C25/30. Angle brackets were obtained from the same section of the beam and fastened to the web of steel beam to provide the shear connection. Two shear connectors were tested namely; “SC1” and “SC2” shear connectors. Both shear connectors showed a ductile behavior and had satisfied the ductility requirements of EN1994-1-1 standard. It was concluded that the ductile behavior of shear connectors could enhance the design of composite beam.