Abstract
After an extended cold weather outage on a distribution circuit supplying a high saturation of electrical space heating, large transient overcurrent's persist for several hours because of the undiversified heating load. In this paper, the electrical space heating component of enduring demand is characterized by a smooth curve. Expressions are derived for the parameters of the curve in terms of the outage conditions and a statistical description of the residences. A method is suggested for using this characterization to determine the effects of a cold load pick up on the distribution circuit components. Copyright © 1982 by The Institute of Electrical and Electronics Engineers, Inc.
Recommended Citation
W. W. Lang et al., "An Analytical Method For Quantifying The Electrical Space Heating Component Of A Cold Load Pick Up," IEEE Transactions on Power Apparatus and Systems, vol. PAS thru 101, no. 4, pp. 924 - 932, Institute of Electrical and Electronics Engineers, Jan 1982.